AEMC DL913

  • 3 channel AC current
  • 3 integral 24-inch flexible current sensors
  • Current measurements from 500 mA up to 3600 A
  • LCD display to view real-time measurements and parameters, configure the instrument, and change viewing modes
  • Built-in web server for remote monitoring
  • Battery and/or USB-powered options
  • Wi-Fi and USB communications
  • Waterproof IP67 rated (USB cap on and the cover closed)
  • Flame retardant case
  • Logged data can be downloaded, analyzed, and formatted into reports using the FREE DataView® software

$1,799.00

Normal delivery 1-2 weeks

Description

AEMC DL913 AC Current Data Logger

The AEMC DL913 AC Current Data Logger is a 3-channel AC current data logger with three integral flexible current sensors. Each sensor is 24 inches long and capable of wrapping around a 7.64-inch conductor. The DL913 has two measurement ranges of up to 300 and 3000 Amps. Both the data logger housing and the current sensors are water resistant and rated to IP 67. A selection of data storage modes, as well as data sampling rates, is user programmable through the DataView® software included with the unit. However, most of the setup can also be done from the keypad and LCD display on the instrument. The measurements are stored in internal nonvolatile memory. Data storage rates as fast as once per second.

Communication is done through a USB port or wireless Wi-Fi and it is powered by two rechargeable NiMH batteries. The instrument can also be externally powered through the USB plug.

Includes small classic tool bag, 10 ft USB Type A to Type B cable, (4) stainless steel mounting brackets with (4) Phillips M4-0.7 x 8 mm stainless steel machine screws, USB power adapter, quick start guide, and USB thumb drive with DataView® software and user manual.

Applications

  • Single/Split-phase and 3- or 4-phase load monitoring
  • Neutral and ground current monitoring
  • Intermittent problem detection
  • Machine load monitoring
  • Fault current detection
  • Load profiling

The DL914 is also available with an added channel for neutral current monitoring

Specifications

Channels Three
Input Captive MiniFlex® AC current flexible sensors
Ranges (2) 300 AAC 3000 AAC
Accuracy (50/60Hz) 0.5 A to 99.99 A ± (1% r +10 D)
90.0 A to 360.0 A ± (1% r +4 D)
4.00 A to 99.99 A (1% r +10 D)
90.0 to 999.9 A (± (1% r +5 D)
0.900 kA to 3.600 kA (± (1% r +4 D)
Resolution 0.01 A to 0.1 A 0.01 A to 1 A
Storage Rate Normal recording mode: Once per second
Extended recording mode: Four per aggregation period
Storage Modes Start/Stop, extended mode
Recording Length Battery Power: 4 days with no missing samples (normal recording mode)
7 to 30 days depending on the selected aggregation period (extended recording mode)
External Power: 365 days
Memory Recorded data is stored in non-volatile 8 GB internal memory.
Communication USB, Wi-Fi direct or via router (Ethernet)
Power Source Internal: (2) 4.2 A·h NiMH rechargeable batteries
External: 5V through USB port
Battery Charge 10 h maximum (Wi-Fi off)
Dimensions (5.9 x 5.9 x 3.57) in (150 x 150 x 91) mm w/o sensor
Weight (with battery) 2.2 lbs (1 kg)
Operating Temperature (14 to 122) °F (-10 to 50) °C
Storage Temperature (-40 to 158) °F (-40 to 70) °C w/o batteries
Relative Humidity Up to 85% RH
Storage Humidity Up to 95% RH
Ingress Protection (IP) IP67 (USB cap on and cover closed)
EMC EN 61326-1
Safety Compliance 600V CAT IV, 1000 V CAT III, IEC 61010-1, EN 61010-2-32

Software

DataView Software – Data Analysis and Reporting Software

Easy to access, download and view real-time and recorded data!

  • Display and analyze real-time data on your PC
  • Configure all data logger functions and parameters from your PC including sample rate, communication, recording length, channel configuration, and more
  • Create and store a library of configurations that can be uploaded to the logger as needed
  • Pan and zoom through sections of the graph to analyze the data
  • Display trend graphs and text summaries
  • Print reports using standard or custom templates you design
  • Free software upgrades are available on their website www.aemc.com

Configuring the data logger’s general communication, recording, and instrument options are simple with the DataView® control panel software.

The top left image represents the communication configuration tab with Wi-Fi enabled.

The recording tab provides sample and storage rate selections, recording length and schedule, session type, and the extended recording mode option.

Downloads