AEMC PEL 52

  • View measurements in real-time for voltage, current, frequency, and power
  • Wide backlit LCD display
  • TRMS voltage and current measurement up to 3000 A (sensor dependent)
  • Phase powered, does not require a separate power source
  • TRMS AC measurements (50 and 60) Hz, aggregation every second without missing measurements
  • W, VA and var (P, Q, S, N and D) power measurements
  • Calculation of the Cos φ and Power Factor (DPF)
  • Aggregation measurements over a period from 1 minute to 1 hour
  • Storage of the 1 s and aggregated measurements on an SD/SDHC card; data can be read directly on a PC
  • Remote connectivity and data viewing via DataViewSync™ (AndroidTM, iOS, Windows, etc.)
  • Includes FREE DataView® software

$1,495.00

Delivery In 4-6 Weeks

Description

AEMC PEL 52 Power & Energy Logger – Low Cost, Portable, and Easy-to-Use

The PEL 52 represents an affordable and user-friendly power and energy data logger, suitable for both single and split-phase applications. It is specifically designed for electricians, engineers, and contractors working in residential and light commercial areas. This device allows effortless measurement, recording, and analysis of crucial energy data. Generating reports is a breeze, requiring minimal configuration time and effort, with the added benefit of having standard and customizable report options available.

The instrument is powered by V1 inputs from (90 to 690) V. Two 800 mAh NIMH batteries supply power if a source is not available.

The instrument’s design enables it to be installed inside a load center panel (including the current sensors) allowing the door to close on most panels. The PEL 52 series energy loggers measure and record one or two True RMS voltage inputs up to 690 V and current inputs up to 3600 A (sensor dependent), Watts, VARS, VA, and Energy (kWh and kVA). Power Factor (PF), Displacement Power Factor (DPF), and Frequency are calculated and recorded as well. All variables are recorded and stored at a one-second interval and on user-selectable demand intervals from 1 to 60 minutes.

By combining energy-saving techniques with detailed power consumption monitoring, residential and commercial builders can gain valuable insights into their energy usage, pinpoint areas for improvement, and monitor their advancements in energy conservation efforts. Ultimately, this results in decreased energy expenses, a diminished environmental footprint, and improved operational efficiency.

Key Features

  • Accurate and reliable: Provides precise readings over time to make accurate assessments of energy consumption
  • Real-time monitoring to identify patterns, monitor changes, and make informed decisions to optimize energy usage
  • Works with a wide range of electrical equipment, systems and residential and light commercial single or split phase measurements
  • Capable of performing load studies in compliance with NEC 220.87
  • Log data over an extended period, to analyze historical trends and identify areas for improvement
  • DataView software included for data analysis and report generation
  • Rugged and durable: withstands the demands of real-world applications
  • Wi-Fi communication and remote viewing with integrated web server (AndroidTM, iOS, Windows, etc.)
  • Compact casing with built-in magnets for mounting easily inside electrical cabinets

Applications

  • Load surveys – Find out how much energy each item of equipment consumes operating at its min/max power level.
  • Energy analysis – Estimate energy consumption before and after the improvements.
  • Energy surveys – The measurements for energy surveys must be performed at several locations on the evaluation site.

Specifications

General
Inputs 2V / 2I
Types of Installations Single-phase, split-phase, or 2 single-phase channels
Recording / Data Storage Rate Unlimited duration (4 GB max recording size) / 1 s to 1 h (Min/Avg/Max)
Network Frequency 45 to 65 Hz
Voltage 10 to 600 V
Electrical
VOLTAGE Range Resolution Accuracy
Vrms (10 to 600) V P to N 0.1 V ± 0.2 % Reading ± 0.2 V
Urms (20 to 1200) V P to P 0.1 V ± 0.2 % Reading ± 0.4 V
Current Measurement @ (50 and 60) HZ Range Resolution Accuracy
Amps (1 V nominal) (excluding clamp accuracy) Probe dependent (0.2 % < I < 120 % Inom) Probe Dependent ± 0.2 % Reading, ± 0.02 Inom
POWER Range Resolution Accuracy
Watts P-Q-S (W-var-VA) V = (10 to 600) V

I = (5 to 120) % Inom

Probe Dependent ± 0.3 % R ± 0.003 %Pnom, ± 1 % R ± 0.01 %Qnom, ± 0.3 % R ± 0.003 % Snom
Power Factor -1 to 1 0.001 ± 0.02 %
Cos φ (DPF) -1 to 1 0.001 ± 0.02 %
ENERGY Range Resolution Accuracy
Ep-Eq-Es (Wh, varh, Vah) V = (10 to 600) V

I = (5 to 120) % Inom

0.001 and ± 0.02% ± 0.5 % Reading

± 1.5 % Reading

± 0.5 % Reading

Mechanical
Communication Wi-Fi (access point and hot spot)
Data Storage 8 GB SD-Card (included); expandable to 32 GB
Dimension (7.08 x 3.46 x 1.45) in (180 x 88 x 37) mm
Weight 14.10 oz (400 g)
Case Compact and rugged, shock and vibration IEC 61010
Display Type LCD with blue backlight
Real-Time Clock Time and date stamp for Trend mode
Power Supply From phase 1 (90 to 660) V battery backup when power OFF
Battery Life 3 h without Wi-Fi, 1 h typical with Wi-Fi enabled
Environmental
Operating Temperature / Relative Humidity (-4 to 122) °F (-20 to 50) °C / (10 to 75) % RH
Storage Temperature (-40 to 158) °F (-40 to 70) °C / (45 to 75) % RH w/out battery
Safety
Electro-Magnetic-Compatibility (EMC) EN 61326-1 for emission and immunity
Safety Rating / CE Rating IEC/EN 61010-2-30 (600 V CAT III) / Yes
IP Rating IP54 per IEC 60529
* Minimum and maximum values are current probe dependent. Consult factory for NIST Calibration prices

Software

DataView – Data Analysis and Reporting Software

The DataView® software simplifies data analysis and report configurations by allowing easy downloading of recorded data onto a PC. Upon connecting a device to a PC, the software automatically identifies it and opens the relevant menu for direct access to the recorded data. Users can quickly edit predefined reports that adhere to standards or create and save their customized reports, views, and instrument settings, saving valuable time in the field.

Configure All Functions of the PEL

  • Improve energy efficiencies by analyzing energy losses
  • Convert energy data directly into costs with configurable monetary value.
  • Display and analyze real-time data on your PC
  • Configure functions and parameters from your PC
  • Control multiple instruments in real time when connected to the same Ethernet network
  • Customize views, templates, and reports to your needs
  • Create and store a robust library of configurations that can be uploaded as needed
  • Analyze data by zooming, panning, and sectioning graphs
  • NEC article 220.87 30-day load study feature
  • Download, display, and analyze recorded data
  • Display waveforms, trend graphs, text summaries, transients, event logs, and stored alarms
  • Print reports using standard or custom templates

Downloads

Documentation

PEL 52 User Manual (PDF)

PEL 52 Quick Start Guide (PDF)

Power Analyzer – Current Probe Selection Chart (PDF)

PEL Series Comparison Chart (PDF)

 

Reviews

There are no reviews yet.

Be the first to review “AEMC PEL 52”